Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/23/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H2.5 TIES MISSING AT PORCH LEDGER 2) FIRESTOP CHASE 2ND FLOOR AT FLEX DUCT 3) REPAIR/FIX WEED SCREED FRONT ENTRY AND CHECK SPECS ON 1-COAT FOR BOND MISSING AT GAS 4) PROTECT WIRES THRU-OUT AS NEEDED 5) PLUMBER TAPE NOT ALLOWED TO SUPPORT ABS PIPES 6) STRAP GLU LAM TO POSTS 1ST FLOOR KITCHEN/DINING 7) FIRESTOP AT GAS PIPE KITCHEN 8) NAIL 3-2 X 4 POST TIGHT, BY REAR DOOR 9) PROTECT ABS PIPES AT STAIRWAY 10) DRIVE NAILS FLUSH AT HIP JOIST HANGE 2ND FLOOR |
|
| 10/20/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL TRADES NOT COMPLETE |