Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/26/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1, 2, 5, 7 & 9 NOT DONE FROM PREVIOUS INSPECTION |
|
| 12/19/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* INTERMEDIATE GROUP 1. REMOVE STAPLES BEHIND HOMERUNS AT UPPER STUD BAY 2. TOP PLATE NOTCH, FOR A/C LINES, NEEDS FHA STRAPS AND DRYER VENT-NAIL ALL HOLES 3. SUPPORT ABS 90 DEG. AT KIT. VENT 4. MOVE PEX 12" FROM CAN LIGHTS 5. SHIM HEADER/TRIMMER CONNECTIONS 6. PLAN CALLS FOR 2-220 OUTLETS + 1-110 OUTLET IN MECH. CLOSET. 7. INSULATE BEHIND TUB SURROUND 8. NO WATER IN DWV TEST (H2O OK) 9. COMPLETE NORTH END GABLE TRUSS X BRACE 10. REPAIR MESH AT TOILET VENT |
|
| 11/21/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |