Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/28/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANTI-SIPHON ON HOSE BIB 2) MOVE WIRE AWAY FROM B-VENT AT WATER HEATER 3) COMPLETE CONDENSATE DRAINS 4) FIRE BLOCK DROP CEILING IN HALLWAY 5) FROM AIR INTAKE WITHIN 10' OF PLUMBING VENT 6) CONNECT UFER 7) VENT AT KITCHEN SINK MUST BE ABOVE FLOOD RIM 8) PROTECT HOOD VENT AT TOP PLATE 9) 1/2" FIRE STOP AT MASTER BATH MUST BE DBL LAYERED 10) SEAL VAPOR BARRIER |