Permit: T06CM01095

Parcel: 115010720


Addresses:

2217 N FLORES DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/24/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/14/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTERIOR SHEATHING NAILS SET TO DEEP (RENAIL ALL)
2) PLAN CALLS FOR SOLID 2 X VENTED BLOCKING WEST WALL
3) 3/4" X 5" BOLTS REQUIRED FOR END BOLTS (SEE APPROVED DRAWING)
06/05/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ITEMS BELOW AND RECALL
2) OK TO DRY IN
3) BRACED WALL PANELS (22) REQUIRE NAILS SPACING 6"-12" AND SOME NAILS SET TOO DEEP AND REQUIRED ANCHOR BOLTS AT QUARTER POINTS
4) HEADER NOT INSTALLED OVER NEW OPENING IN EXISTING BRICK WALL 2 X BLOCKING WITH SCREENED VENTS REQUIRED FULL HEIGHT
5) PLAN CALLS FOR 2" X 8" FASCIA
6) FURRING INCOMPLETE BRICK WALL