Permit: T06CM01082

Parcel: 141096300

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01082

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2006 FRAMING Approved IVRS - Inspection :*
12/06/2006 FRAMING Partial Approval IVRS - Inspection :*
11/21/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 2 1/2" CLEANOUT AT M. TOILET SEE PLAN
2) PROVIDE 2 1/2" CLEANOUT AT HALL TOILET
3) BEARING STUDS OVER BORED AT KITCHEN 4050 INSTALL STUD SHOES
4) KITCHEN SHEAR WALL STOPS 1 1/2" BELOW TRUSSES DOES NOT PROVIDE POSITIVE CONNECTION