Inspection History: FRAMING

Permit Number - T06CM01079

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2007 FRAMING Approved IVRS - Inspection :*
01/16/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1 & 2 FROM 1/9/07 NOT DONE
01/09/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATH FOAM BOARD HAS BEEN EXPOSED TO SUN FOR MORE THAN 180 DAYS. HAVE MANUFACTURER ENGINEER EVALUATE SERVICE ABILITY AND RECOMMEND CORRECTIVE ACTION FOR SEVERAL YELLOWING
2) W/H B-VENT MUST BE 1" FROM COMBUSTIBLE MATERIAL
3) LEAK AT POWDER ROOM
4) MIS ALIGNED AND EXTERNALLY GLUED FITTING AT POWDER ROOM LAV AND TRAP WEIR HIGHER THAN VENT OPENING
5) WINDOW STOPS HAVE MORE THAN 3/8" DIFFERENCE IN RISE
6) A/C PRIMARY OUT OF WALL
7) A/C SECONDARY MUST BE IN CONSPICOUS LOCATION
8) FIRESTOP B-VENT
9) STAIR LIGHT NOT 6'-8"