Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01079
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
06/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE OFF SITE AND ON SITE FRAMING OF THIS HOUSE WAS DONE USING 3" X .131" 10D FRAMING NAILS-16D NAILS ARE REQUIRED. HAVE ENGINEER OF RECORD PROVIDE CITY OF TUCSON AN EVALUATION AND RESOLUTION TO THE PROBLEM 2) TECO NAILS CANNOT BE USED TO SECURE HARDWARE THRU OSB. YOU MUST USE 8D COMMON OR SINKERS 3) SAFETY BRACES MUST USE 16D NAILS 4) PORCH LEDGER REQUIRES BLOCKS, H2.5 CLIPS AND HAVE LEDGER DIRECTLY CONNECTED TO STUDS 15/D7 |