Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 11/16/2006 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC PORTION OF TRANSITION HAS HAD PRIMER PAINTED OVER TRANSITION GLUE 2) HAVE TRANSITION FITITNG REMOVED AND REPLACE WITH PROPER INSTALLATION |
|
| 10/26/2006 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC PORTION OF TRANSITION FITTING REQUIRES PRIMER-REPLACE FITTING 2) SEWER LINE MUST CONTINOUSLY BEAR ON COMPACTED SOIL |