Permit: T06CM01071

Parcel: 141096190

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
12/29/2006 BUILDING - FINAL Approved IVRS - Inspection :*
12/26/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PVC CLEAN OUT
2) WIRES DAMAGED BY OVER TORQUING ELECTRIC SERVICE LUGGED. REPAIR ALL DAMAGED WIRES. SEE PANEL FOR PROPER TORQUE
3) LABEL ALL CIRCUITS IN PANEL
4) MAX ALLOWED FUSE FOR A/C 30 AMP-60 INSTALLED
5) SEAL GARAGE FIREWALL AT GAS LINE AND COLD WATER
6) KITCHEN GFCI INOPERABLE
7) MASTER BEDROOM ELECTRIC OUTLETS GREATER THAN 12 FEET APART