Permit: T06CM01066

Parcel: 115170980

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/29/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER SUBJECT TO REVISION OF MATERIAL TYPE AND PIPE INSULATION SPECS. PIPING IS NOT INSULATED
NEED TO REINSPECT CLOSET FLANGES AFTER FINISHED FLOOR
08/14/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/13/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR TYPE "L" COPPER WITH HOT PIPING INSULATED - NOT INSTALLED PER PLAN
2. 1 1/2" TRAP ARMS MAY NOT EXCEED 3'6" AND ARE TO BE INSTALLED WITH 1/4" PITCH PER FOOT
3. FILL TUBS PAST OVERFLOW
4. REQUIRE 18" OF COPPER AT WATER SERVICE AND WATER HEATER
5. ALL PIPING (INCLUDING GAS) TO BE SUPPORTED PER
TABLE 3-2 2003 UPC VERTICAL PIPE SUPPORT/HORIZONTAL PIPE SUPPORT

NOTE: LAYING PIPE ON 2" X 4" 's OR STRUNG THRU JOIST MEMBERS IS NOT SUPPORT
08/10/2007 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled