Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM01066
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/16/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER SUBJECT TO REVISION OF MATERIAL TYPE AND PIPE INSULATION SPECS. PIPING IS NOT INSULATED NEED TO REINSPECT CLOSET FLANGES AFTER FINISHED FLOOR |
|
| 08/14/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/13/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR TYPE "L" COPPER WITH HOT PIPING INSULATED - NOT INSTALLED PER PLAN 2. 1 1/2" TRAP ARMS MAY NOT EXCEED 3'6" AND ARE TO BE INSTALLED WITH 1/4" PITCH PER FOOT 3. FILL TUBS PAST OVERFLOW 4. REQUIRE 18" OF COPPER AT WATER SERVICE AND WATER HEATER 5. ALL PIPING (INCLUDING GAS) TO BE SUPPORTED PER TABLE 3-2 2003 UPC VERTICAL PIPE SUPPORT/HORIZONTAL PIPE SUPPORT NOTE: LAYING PIPE ON 2" X 4" 's OR STRUNG THRU JOIST MEMBERS IS NOT SUPPORT |
|
| 08/10/2007 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled |