Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/01/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL UNUSED OPENING IN SERVICE 2. SERVICE DISCONNECTS TO BE IDENTIFIED AS UNITS ARE 3. IDENTIFY "SERVICE DISCONNECTS" AS SUCH - NEC 230.72B 4. BONDING CONDUCTOR TO RISER UNDERSIZED - NEC 250.102C 5. NEEL COMPOUND AL ALUMINUM 6. ALL STRANDS OF CONDUTOR TO BE UNDER TERMINATION 7. DIFFERENT SIZED GROUNDS NOT ALLOWED UNDER SAME TERMINATION |
|
| 03/25/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL ALL UNUSED OPENINGS 2. INSTALL ALL BREAKERS 3. NEED JOINT COMPOUND ALL ALUMINUM TERMINATIONS GO THROUGH ALL SERVICES AND PANELS TO MAKE SURE ALL IS READY 4. BOND SERVICE RISERS 5. ALL CONDUCTOR STRANDS TO BE UNDER TERMINATIONS 6. WIRE FEEDERS ALL EQUIPMENT TO BE OPEN FOR INSPECTION |