Permit: T06CM01066

Parcel: 115170980

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROTECT ROOF PENETRATIONS
2. #10 ROMEX (DRYER) DOES NOT FIT IN CAVITY DUE TO DRYER OUTLET VENT (MIDDLE UNIT)
08/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOF PENETRATIONS FOR AC FEEDER REQUIRES CONDUIT SLEEVE
2. TOP WOODEN 2X4 PLATE ABOVE PANEL - USE NAIL PROTECTIVE PLATES WHERE LESS THAN 1 1/4"
3. STAPLE ALL ROMEX WIRES ABOVE PANEL
4. #12 ROMEX BEHIND DRYER VENT IS FORCED TO STICK OUT OF WALL, ALL UNITS
5. ALL EXTERIOR BOXES TO BE PLACED TO MEET O/S DEPTH OF WALL
08/10/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COULD NOT LOCATE PLANS/PERMIT