Permit: T06CM01064

Parcel: 115170980

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01064

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
EAST UNIT
1. NAIL PLATES ARE NEEDED IN SEVERAL LOCATIONS
WHEREVER HOLE IS 1 1/4" OR LESS FROM EITHER SIDE OF STUD FACE
2. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES ON GROUNDS
3. FINISH PHONE AND TV WIRING
4. HAVE UNMOUNTED BOX IN KITCHEN AREA
5. REFRIDGE J-BOX OVERFILLED
6. KITCHEN 3-GANG SWITCHBOX OVERFILLED
7. USE LIGHT BOXES FOR FIXTURES INSTEAD OF RECEPTACLE BOXES

WEST UNIT
1. BEDROOM SMOKE DETECTOR TO BE 36" AWAY FROM HVAC VENT
2. CHECK FOR #1,2,3, 4, 7 FROM EAST UNIT INSPECTION

ALSO, KITCHEN COUNTER RECEPTACLES TO BE ABOVE COUNTERTOPS -- NOT BEHIND SINK -- CHECK LAYOUT
HAVE PLANS ON SITE