Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* EAST UNIT 1. NAIL PLATES ARE NEEDED IN SEVERAL LOCATIONS WHEREVER HOLE IS 1 1/4" OR LESS FROM EITHER SIDE OF STUD FACE 2. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES ON GROUNDS 3. FINISH PHONE AND TV WIRING 4. HAVE UNMOUNTED BOX IN KITCHEN AREA 5. REFRIDGE J-BOX OVERFILLED 6. KITCHEN 3-GANG SWITCHBOX OVERFILLED 7. USE LIGHT BOXES FOR FIXTURES INSTEAD OF RECEPTACLE BOXES WEST UNIT 1. BEDROOM SMOKE DETECTOR TO BE 36" AWAY FROM HVAC VENT 2. CHECK FOR #1,2,3, 4, 7 FROM EAST UNIT INSPECTION ALSO, KITCHEN COUNTER RECEPTACLES TO BE ABOVE COUNTERTOPS -- NOT BEHIND SINK -- CHECK LAYOUT HAVE PLANS ON SITE |