Permit: T06CM01063

Parcel: 115170980

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM01063

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SECURE WATER STUB OUTS PERPENDICULAR W/WALL
OK TO COVER WALLS

03035 LEFT OPEN FOR MATERIAL SPECIFICATIONS AND CLOSET FLANGE INSP.
08/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- DWV OK
- 18" OF METALLIC PIPE REQUIRED AT WATER SERVICE
SEE PLUMBING SPECS L CU SPECIFIED AND 1" FIBERGLASS INSULATION.
- PROVIDE WATER PRESSURE GAUGE
- SECURE SHOWER VALVES
- SECURE PEX TO BLOCKING W/APPROVED CLAMPS
NOT ZIP TIES
- SECURE WASHER BOX VALVES
- CORRECT PEX AT LAV UNIT 2
- SUPPORT HORIZONTAL GAS PIPING
- SUPPORT NEAR ROOF PENETRATIONS
- WHS INSTALLED ON A WOOD PLATFORM REQUIRE A PAN
- SECURE SUPPORTS AT VENTS ABV TUBS

CLOSET FLANGES SHALL BE INSPECTED AFTER FINISHED FLOOR. FLANGES SHALL BE SECURED TO FF