Permit: T06CM01062

Parcel: 115041280


Addresses:

1316 N TYNDALL AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01062

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2006 FRAMING Approved IVRS - Inspection :*
10/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCK FOR LATHE TOP PLATES WHERE NEEDED
2) FASTEN LATHE 6" ON CENTER CARPORT TOP PLATE AND ENTRY DOOR, FRONT DORMERS NOT COMPLETE, FASTEN REAR PORCH TOP PLATE 6" ON CENTER AND RE-INFORCE ALL DOORS AND WINDOWS
3) SHIM BEARING HEADERS
4) RESTRICTED FLEX DOWNSTAIRS WEST BATH
5) FIRE STOP TUB SHOES
6) BLOCK REGISTER BOOT 3 SIDES UPSTAIRS CLOSETS
7) FIRE BLOCK DROP UPSTAIRS BED 3 SOFFIT
06/29/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATHE MUST BE COMPLETE PRIOR TO INTERMEDIATES
2) COMPLETE FRAMING INSPECTION NOT COMPLETED
3) S/D NEED TO BE MINIMUM 3' FROM A/C SUPPLY
4) ALL ABS MUST BE SUPPORTED EVERY 5'
5) AIR ADMITTANCE VALVE MUST BE ACCESSIBLE
6) PEX MUST BE MINIMUM 12" FROM RECESSED CANS
7) AN OVERFLOW PAN OR AN AUTOMATIC SHUT OFF FOR CONDENSATE OVER FLOW IS REQUIRED
8) DWV TEST NOT FULL