Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01058
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. CIRCUITRY APPEARS TO HAVE BEEN CHANGED AS PER PLAN ALSO, PNL CL DIRECTORY NOT AS PER PLAN. 2. PROPERLY SUPPORT ALL COMMUNICATIONS WIRING ABOVE CEILING SOME HANGING THRU CEILING. 3. MISSING DEVICE COVER WEST WALL & SOME MISSING J-BOX COVERS UNDER DESKS. 4. ALL GFI'S TO BE WORKING PROPERLY 5. SUPPORT LOOSE MC CABLE UNDER DESK 6. PROPERLY CLOSE OFF OPEN WIRING IN CHEM STORAGE 7. FINISH AUTO FLUSH DEVICE MEN'S TOILETS. |
|
| 08/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |