Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2008 | ELECTRIC - FINAL | Approved | CONTR. REQUEST AFTER HRS. INSP. $150.00 PAID CK#1231 |
|
| 02/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PER LATEST REVISION - NO ELECTRICAL |
|
| 12/19/2007 | ELECTRIC - FINAL | Denied | ALL ELECTRIC ON THIS SHELL ACTIVITY MUST BE INSPECTED AND APPROVED BY ELECTRICAL INSPECTOR. OUTDOOR LIGHTING MUST MATCH PLAN. | |
| 12/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - UFER CUT, USE GROUND RODS APPROVED BY ARCH. - OUTSIDE LTG. NOT PER PLAN - 2 GFI RECEPTS OUTSIDE PER PLAN - BOND WATER & GAS PIPING - REVISE PLAN FOR SERVICE ARRANGEMENT |