Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM01024
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/04/2006 | PLUMBING - FINAL | Cancelled | CANCELLED HAND WRITTEN REQUEST PER JILL OF VENTURE WEST #722-9292 | |
| 11/29/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* MED GAS COMPLETE. ALL AREAS EXCEPT FOR SINKS IN RMS 214 AND 215 WHICH ARE NOT INSTALLED, AND PLAN REVISION FOR USE OF AAVS ARE COMPLETE. I SEE NO HAZARDS THAT WOULD PREVENT TCO. |
|
| 11/22/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MED GAS FINAL NEEDED 2) CLEANOUT MISSING AT SINK ROOM 210 3) SEVERAL FIXTURES P-3, P-4 AND P-7 ARE INSTALLED WITH AAVS, PLAN SPECIFIES VTR FOR THESE FIXTURES 4) ROOMS 214 AND 215 FIXTURES NOT INSTALLED, PIPING HAS TEMP CAPS |