Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM01024
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CLOSET FLANGES OK |
|
| 10/30/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* INSTALL CLOSET FLANGES PER INSTALLATION STANDARDS. |
|
| 09/20/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* IN WALLS OK CLOSET FLANGES NOT COMPLETE |
|
| 09/18/2006 | PLUMBING - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR JILL #722-9292 | |
| 09/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PROTECT CU FROM WIRE & STUCCO - SECURE CLOSET FLANGES W/FASTENERS - SWEEPS REQUIRED ON TRAP ARMS - JOINTS ON PIPE INSULATION SHALL BE NEATLY SEALED W/LAGGING ADHESIVE. - MEDICAL AIR INSTALLED AND UNDER TEST. INSTALLER NOT ON SITE. - LABELS IN WALL OK |