Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01024
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MAINTAIN WORKING SPACE AT DISCONNECTS 110.26 2) EXIT AND EM LIGHTING TO BE ON AREA SERVED 700.12 3) WAITING ON REVISED DRAWINGS FOR SERVICE 4) LABEL BREAKERS TO AREAS 5) PLEASE REVISE LIGHTING SCHEDULE AND ? ? ? 6) OK WATER BOND AND ELECTRIC CABINETS |
|
| 09/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS SUBJECT TO A LETTER AUTHORIZING USE OF M/C CABLE -- PLANS STATE NOT ACCEPTABLE. |
|
| 09/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT VDV CABELING IN WALLS 2. STRAP M/C CABLE UPON EXITING WALLS 3. TIGHTEN LOOSE FITTINGS 4. SUPPORT FLEX CONDUITS 12" & 4' OK SOUTH, EAST AND WEST EXTERIOR WALL EXCEPT AS NOTED. |
|
| 08/17/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS |
|
| 08/16/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL LIGHTS OUTSIDE |