Permit: T06CM01024

Parcel: 110102410

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01024

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/29/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAINTAIN WORKING SPACE AT DISCONNECTS 110.26
2) EXIT AND EM LIGHTING TO BE ON AREA SERVED 700.12
3) WAITING ON REVISED DRAWINGS FOR SERVICE
4) LABEL BREAKERS TO AREAS
5) PLEASE REVISE LIGHTING SCHEDULE AND ? ? ?
6) OK WATER BOND AND ELECTRIC CABINETS
09/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS SUBJECT TO A LETTER AUTHORIZING USE OF M/C CABLE -- PLANS STATE NOT ACCEPTABLE.
09/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABELING IN WALLS
2. STRAP M/C CABLE UPON EXITING WALLS
3. TIGHTEN LOOSE FITTINGS
4. SUPPORT FLEX CONDUITS 12" & 4'

OK SOUTH, EAST AND WEST EXTERIOR
WALL EXCEPT AS NOTED.
08/17/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO WORK PROGRESS
08/16/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL LIGHTS OUTSIDE