Permit: T06CM01015

Parcel: 12111160A


Addresses:

1622 N SWAN RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM01015

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2006 PLUMBING - FINAL Approved
09/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
WATER HEATER AND WH SAFETY DEVICES ARE OK
INSULATE HW AND HW RECIRC PIPING AT WH
HB VAC BREAKERS MISSING
MIXING VALVE AT FILE PROCESSOR MISSING.
PROVIDE BACKFLOW CERT FOR INTERNAL
CLEANOUT PLUGS FOR SINKS SHALL BE REMOVABLE WITHOUT HAVING TO CUT SHEET ROCK
09/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLUMBING FIXTURES DO NOT MEET PLAN SPECS, SOME EXAMPLES ARE WCS, LAVS, LAV FAUCETS, MOP SINK FAUCET.
LOOSE KEY ANGLE STOPS. PROVIDE LETTER FROM ENGINEER FOR THIS PROJECT, ALLOWING BRAND OF FIXTURES INSTALLED.

ALL FIXTURES SHALL BE SEALED WHERE CONTACTING FLOOR, WALLS AND COUNTER TOPS. THIS INCLUDES ALL SINKS, LAVS & WCS
SUPPORT EXP. TANK
TERMINATE T&P
INSTALL HB VAC BREAKERS
LOCATE 3" FCO, END OF LINE CLEANOUT SHOWN ON PLAN.
TRIM OUT ALL CLEANOUTS MAKE THEM ACCESSIBLE
USE PLUGS LISTED TO RECEIVE SCREW FROM COVER.
NOT TAPPING PLASTIC PLUGS
PLUMBER THAT INSTALLED NEW RP IS TO OBTAIN PERMIT FROM TUCSON WATER BACKFLOW SECTION.