Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM01015

Parcel: 12111160A


Addresses:

1622 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01015

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - FINAL Approved
12/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/20/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
11/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUPPORT WIRES NEEDED ON CANS
2) ATTACH FIXTURE TO GRID 410.16 2 ON CENTER OR 4 ON CORNERS
3) PLANS CALL FOR 200 AMP DISCONTING MEANS WITH 150 AMP OVER CURRENT DEVICE WITH 4/0 COPPER WIRE-WE HAVE 100 AMP/100 AMP WITH #2 CONDUCTOR-VERIFY PER 517.72 & 517.73
4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20
5) USE LISTED AND APPROVED GROUND SCREWS
6) PLEASE VERIFY ? GROUND PER 517.13
7) PROPERLY TERMINATE CONDUCTORS TO TERMINAL SCREWS
8) FINISH PREVIOUS ITEMS #1
11/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY INSPECTION TO CLOSE WALLS FOR ELECTRIC IF NOT PLEASE OPEN FOR INSPECTION -
X-RAY ROOM
2. LIGHTING IN X-RAY ROOM NOT AS PER PLANS.

X-RAY ROOM IS IN USE WITHOUT ANY INSPECTION.
09/18/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/18/2006 ELECTRIC - FINAL Partial Approval 1. PROVIDE REJECTION PINS AT SERVICE DISCONNECTS
2. LABEL DISCONNECT IN FILE ROOM
3. LOCK OUT OR SECURE OLD METER FACE PLATES
4. FINISH X-RAY ROOM

OK TCO SUBJECT TO DETERMINATION OF STEVE LONG.
09/11/2006 ELECTRIC - FINAL Partial Approval 1) LABEL ALL DISCONNECTS
2) FINISH X-RAY ROOM
3) FINISH PREVIOUS ITEMS
09/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH SERVICE
2. BONDING TO BE PER 250.102
3. INSTALL GROUNDING ELECTRODE SYSTEM AS DISCUSSED
09/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRICAL AS DISCUSSED
09/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. VERIFY LISTING FOR EXAM TABLES FOR ELECTRIC
2. FINISH WATER HEATER CLOSET
3. ONLY ONE CONDUCTOR TO A LUG
4. SHEET METAL SCREW NOT ALLOWED FOR GROUNDING 230.8
5. CLEAN SURFACE UNDER LUG 250.12
6. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED.
7. CORRECTLY AND LEGIBLY LABEL PANEL DIRECTORIES
8. PLEASE VERIFY EXIT LIGHTS FOR EMG. BACK UP NOT WORKING.
9. BREAKER TO BE LISTED FOR USE BY MANUFACTURER
10. WALL FIXTURES TO BE LISTED & LABELED.