Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01015
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2007 | ELECTRIC - FINAL | Approved | ||
| 12/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 11/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT WIRES NEEDED ON CANS 2) ATTACH FIXTURE TO GRID 410.16 2 ON CENTER OR 4 ON CORNERS 3) PLANS CALL FOR 200 AMP DISCONTING MEANS WITH 150 AMP OVER CURRENT DEVICE WITH 4/0 COPPER WIRE-WE HAVE 100 AMP/100 AMP WITH #2 CONDUCTOR-VERIFY PER 517.72 & 517.73 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 5) USE LISTED AND APPROVED GROUND SCREWS 6) PLEASE VERIFY ? GROUND PER 517.13 7) PROPERLY TERMINATE CONDUCTORS TO TERMINAL SCREWS 8) FINISH PREVIOUS ITEMS #1 |
|
| 11/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY INSPECTION TO CLOSE WALLS FOR ELECTRIC IF NOT PLEASE OPEN FOR INSPECTION - X-RAY ROOM 2. LIGHTING IN X-RAY ROOM NOT AS PER PLANS. X-RAY ROOM IS IN USE WITHOUT ANY INSPECTION. |
|
| 09/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/18/2006 | ELECTRIC - FINAL | Partial Approval | 1. PROVIDE REJECTION PINS AT SERVICE DISCONNECTS 2. LABEL DISCONNECT IN FILE ROOM 3. LOCK OUT OR SECURE OLD METER FACE PLATES 4. FINISH X-RAY ROOM OK TCO SUBJECT TO DETERMINATION OF STEVE LONG. |
|
| 09/11/2006 | ELECTRIC - FINAL | Partial Approval | 1) LABEL ALL DISCONNECTS 2) FINISH X-RAY ROOM 3) FINISH PREVIOUS ITEMS |
|
| 09/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH SERVICE 2. BONDING TO BE PER 250.102 3. INSTALL GROUNDING ELECTRODE SYSTEM AS DISCUSSED |
|
| 09/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ELECTRICAL AS DISCUSSED |
|
| 09/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. VERIFY LISTING FOR EXAM TABLES FOR ELECTRIC 2. FINISH WATER HEATER CLOSET 3. ONLY ONE CONDUCTOR TO A LUG 4. SHEET METAL SCREW NOT ALLOWED FOR GROUNDING 230.8 5. CLEAN SURFACE UNDER LUG 250.12 6. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 7. CORRECTLY AND LEGIBLY LABEL PANEL DIRECTORIES 8. PLEASE VERIFY EXIT LIGHTS FOR EMG. BACK UP NOT WORKING. 9. BREAKER TO BE LISTED FOR USE BY MANUFACTURER 10. WALL FIXTURES TO BE LISTED & LABELED. |