Permit: T06CM01015

Parcel: 12111160A


Addresses:

1622 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM01015

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - ABOVE CEILING Approved
12/28/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/20/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/11/2006 ELECTRIC - ABOVE CEILING Partial Approval
08/30/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE EXCEPT AS NOTED
1. FINISH SUPPORTING VDV CABLEING
08/28/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
OPEN UP CEILING TILE TO INSPECT ALL AREAS
08/22/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABLES TO BE INDEPENDENTLY SUPPORTED NOT WRAPPED AROUND CONDUITS.
2. SUPPORT WHIPS UP OFF OF GRID
3. MANUFACTURERS CLIPS MUST BE EFFECTIVE 2X2'S
4. MISSING JUNCTION BOX COVER
5. SUPPORT FLEX CONDUIT IN MED ROOM

OK 2X4'S
08/07/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/12/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
AS DISCUSSED