Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNBUNDLE CONDUCTORS MAX 24" 2) CONDUCTORS (ROMEX) STAPLED ON EDGE 3) PROTECT ROMEX WITH NAIL PLATES 4) COMPLETE MAKE UP OF ALL BOXES |
|
| 11/01/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSPECTED CONDUIT AND PEX WATER LINES IN MASONRY WALL -INTEGRA-WILL CALL BACK WHEN READY FOR REVISED ROUGH PLUMBING-NO DWV TEST. CONTRACTOR HAS BEE ADVISED THAT HE IS RESPONSIBLE IF IT FAILS AT DWV TEST |