Permit: T06CM01007
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 07/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTINGS 2. FINISH #2 PREVIOUS INSPECTION 3. A GROUNDING EQUIPMENT CONDUCTOR AS PER 250.32(B)(1) AND AS PER PLANS |
|
| 04/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH PREVIOUS ITEMS * A REFEE MAY BE ASSESSED FOR UNNECESSARY INSPECTIONS PER ADMIN. CODES |
|
| 04/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE IS ILLUMINATION FOR PANEL 110.26(D) 2. PROTECT CONDUCTORS AT FITTING 300.4 3. NO PLANS ON SITE 4. PLEASE HAVE ELECTRICIAN PRESENT WITH A LADDER TO ACCESS EQUIPMENT FOR INSPECTION ALSO, NEED PREVIOUS WRITE UP TO VERIFY UFER |