Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM00999

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
WASTE & VENT THRU ROOF WATER TEST OK
WATER PIPING OK
CLOSET FLANGE OK
03/14/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AIR OR WATER TEST THRU ROOF FOR WASTE & VENT PIPE
2. REATTACH EXTERIOR GROUND CLAMP AT SERVICE FOR WATER.
3. MAXIMUM DISTANCE FROM DRAIN ENTRY TO WORK OF P.TRAP TO BE 42" WITH LONG RADIUS DRAINAGE FITTINGS REQUIRED FOR HORIZONTAL CHANGE OF DIRECTION.
4. YOUR APPROVED PLAN DOES NOT SHOW AN INSTANT HOT WATER HEATER, THIS DEVICE CANNOT BE THE SOLE CONTROL OF TEMPERATURE NOT TO EXCEED 120 DEGREES AT A PUBLE LAV.