Permit: T06CM00994

Parcel: 134162440

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/21/2006 FRAMING Approved IVRS - Inspection :*
09/21/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR MESH AT DRYER DUCT CHANGE AND CAULK FASCIAS
2) REPAIR FRAME OVER FRONT DOOR
09/19/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE STAPLES BEHIND HOME RUNS
2) NEED 1" CLEARANCE TO WATER HEATER FLUE
3) GAS PRESSURE READS 2 POUNDS
4) DRYER DUCT IS TOO LONG AND OUT OF WALL
5) BANG PLATE STOVE WIRE
6) NEED DETAIL ON KITCHEN SINK PASS THROUGH FRAME AND ADJACENT DOOR FRAME
7) STOPPED INSPECTION