Permit: T06CM00991

Parcel: 131010460


Addresses:

5028 E 22ND ST #106

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/01/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/10/2006 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOT READY MECH. CONTRACTOR MEET ME FOR NEXT INSP.
06/05/2006 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
T-WYES NOT INSULATED AS NOTED ON PREVIOUS INSPECTION.
DUCT & FITTINGS STILL LAYING ON GRID. DO NOT USE A HOLE CUT THRU SHEETROCK TO SUPPORT DUCT & DO NOT USE WIRE OR PANDUIT STRAPS FOR SUPPORT. REMOVE ANY KINKS IN FLEX DUCT. MECH. CONTRACTOR MUST BE ON SITE FOR NEXT INSPECTION.
05/17/2006 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSULATE ALL EXPOSED SHEET METAL FITTINGS
STRAP ALL FLEX DUCT OFF OF CEILINGS EVERY 5' W/1 1/2"
WIDE HANGER STRAP. DO NOT USE ZIP TIES TO STRAP UP FLEX. REPAIR FLEX DUCT CONNECTIONS THAT HAVE COME APART. REMOVE ABANDONED DUCT & BLANK OFF AT PLENUM. REMOVE DIPS & SAGS IN FLEX DUCT. PROVIDE CONDENSATE DRAIN LINE AS INDICATED ON PLANS.