Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* APPROVED FOR SUITE #106 PLAN 6/1/06 |
|
| 07/17/2006 | PLUMBING - FINAL | Cancelled | CANCELLED PER CONTRACTOR DAVID LOWE #260-2255 VIA PHONE AT 9:09 AM | |
| 07/17/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* RECEIVED OK FOR PEX WATER SUPPLY USE FROM RICK BRIGHT. COMPLETE ALL ITEMS LISTED ON 7/10/06 INSPECTION. NOT: THERE HAS BEEN (2) REVISIONS TO APPROVED PLAN AND NONE ARE THE ACTUAL BUILDING INSTALLATION ON THIS SITE. |
|
| 07/10/2006 | PLUMBING - FINAL | Partial Approval | 1. PROVIDE CORRECT CONDENSATE TERMINATION INTO LAV FOR 1" DRAIN PIPING FROM ROOFTOP UNITS. 2. PROVIDE TEMPERING OF HOT WATER TO PUBLIC USE LAVS PER PLAN + 2003 UPC REQUIREMENT. 3. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS. CALL IN 03035 & 03090 FOR FINAL. |