Permit: T06CM00991

Parcel: 131010460


Addresses:

5028 E 22ND ST #106

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/01/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
APPROVED FOR SUITE #106 PLAN 6/1/06
07/17/2006 PLUMBING - FINAL Cancelled CANCELLED PER CONTRACTOR DAVID LOWE #260-2255 VIA PHONE AT 9:09 AM
07/17/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
RECEIVED OK FOR PEX WATER SUPPLY USE FROM RICK BRIGHT. COMPLETE ALL ITEMS LISTED ON 7/10/06 INSPECTION.
NOT: THERE HAS BEEN (2) REVISIONS TO APPROVED PLAN AND NONE ARE THE ACTUAL BUILDING INSTALLATION ON THIS SITE.
07/10/2006 PLUMBING - FINAL Partial Approval 1. PROVIDE CORRECT CONDENSATE TERMINATION INTO LAV FOR 1" DRAIN PIPING FROM ROOFTOP UNITS.
2. PROVIDE TEMPERING OF HOT WATER TO PUBLIC USE LAVS PER PLAN + 2003 UPC REQUIREMENT.
3. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBS. CALL IN 03035 & 03090 FOR FINAL.