Permit: T06CM00991

Parcel: 131010460


Addresses:

5028 E 22ND ST #106

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/05/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/17/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND WASTE & VENT ONLY FOR RESTROOM 19&20
1. NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE.
2. PROVIDE CORRECT BACKFLOW CERTIFICATION FOR EQUIPMENT BEING USED AT SOUTHEAST EXTERIOR OF YOUR SUITE.
05/11/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
STILL NOT SUITE ADDRESS. READ ALL NOTES AND COMPLY OR EXPECT TO PAY REFEE.
NOTE: A DOUBLE SANTEE IS NOT CORRECT FITTING FOR BACK TO BACK STOOLS.
05/04/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES ABOVE FROM 4/17/06
PROVIDE APPROVED FITTINGS AND METHODS FOR ALL PLUMBING SYSTEMS WITH TESTING IN PLACE AT TIME OF INSPECTION. HAVE YOUR PLUMBER ON SITE AT FUTURE INSPECTION.
04/17/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POST SUITE ADDRESS.
2. EXPOSE ALL PLUMBING WORK, PROVIDE TESTING WITH INSPECTION. PROVIDE APPROVED PLAN OF ALL PLUMBING OR REMOVE IT. PROVIDE WORK SHOWN ON PLAN.