Permit: T06CM00991

Parcel: 131010460


Addresses:

5028 E 22ND ST #106

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/11/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/17/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AT ADA MENS BATHROOM I WILL NEED THE WALL OPENED UP TO INSPECT ALL OF THE ELEC. CONDUIT AT SWITCH, RECEPTACLE, LIGHT & EXH. FAN.
2. CONDUIT & NM CABLE TO BE SUPPORTED THROUGHOUT
(MC CABLE TOO).
3. ALL FIXTURES TO BE SECURED WITH SEISMIC SUPPORT WIRES, SCREWED TO THE GRID, AND THE FIXTURE CLIPS MUST BE ATTACHED TO GRID.
4. PHONE - DATA CABLED TO BE SECURED PER NATIONAL ELEC. CODE.
5. ALL EQUIP. TO HAVE PROPER SIZED BREAKERS OR FUSES.
6. LABEL ALL CIRCUITS.
7. ALL EQUIPMENT TO BE PROPERLY GROUNDED.
8. SEAL ALL UNUSED OPENINGS.
9. ONLY CODE APPROVED WIRING METHODS WILL BE ACCEPTED NEED A LIC. ELECTRICAL CONTRACTOR TO COMPLETE ALL CORRECTIONS PROVIDE NAME, PHONE #, CONTACT PERSON AT NEXT INSPECTION.
10. OPEN SPLICES NOT ACCEPTABLE.
11. OPEN DRYWALL SO I CAN SEE ALL NEW WIRING.