Permit: T06CM00990

Parcel: 131010460


Addresses:

5028 E 22ND ST #112

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/01/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/17/2006 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXTEND DOUBLE WALL WATER HEATER VENT DOWN & THRU CEILING, THEN CONNECT WITH SINGLE WALL.
PROVIDE 1" CLEARANCE TO COMBUSTIBLES AT ROOF PENETRATION.
PROVIDE CONDENSATE DRAIN LINE AS INDICATED ON PLANS.
STRAP ALL FLEX EVERY 5'. REMOVE DIPS & SAGS AS MUCH AS POSSIBLE.