Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2008 | BUILDING - FINAL | Approved | LETTER OF COMPLETION ONLY FOR REPAIRS AND REMODEL. | |
| 08/21/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL CIRCUITS MAIN PANEL 2) SECURE #4 TO BLDG 3) SEAL KNOCKOUT CIRCUITS 14 PANEL 4) EXTERIOR GFCI'S NOT UNDER ROOF MUST BE BUBBLE TYPE 5) MISSING EXTERIOR LIGHT FIXTURE REAR 6) GFCI PROTECT KITCHEN OUTLETS 7) PROVIDE WORKING SMOKIES HALLWAY AND BEDROOMS 8) MISSING COVER PLATE 220 STOVE 10) WHITE HOT LEAD 30 AMP MUST BE BLACK OR RED 11) NO POWER TO INTERIOR OUTLETS THROUGHOUT 12) NO PLANS OR PERMIT FOUND |
|
| 07/14/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/23/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* FINALS NOT READY 1. MAKE UP ALL ELECTRIC FOR FINAL 2. INSTALL REGISTERS 3. REINSTALL AIR CONDITIONER 4. FINISH PLUMBING 5. GAS PRESSURE TEST REQUIRED @ FINAL RECALL WHEN DONE |