Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM00985
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
05/23/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/27/2006 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* OK TO COVER FRONT AREA FLOOR BOXES & PVC |