Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM00976
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* CONTR. IS INST. COND. PUMP FOR UNITS. HE'S UNABLE TO PROVIDE A WORKABLE DRAIN INTO PLUMB. SYSTEM. |
|
| 11/02/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOTH APARTMENTS: ISOLATE SUPPLY FLEX DUCT FROM TOUCHING FURNACE VENT PIPE 2) CONDENSATE PIPING, RUN NOW BEFORE WALLS ARE ROCKED 3) WATER HTR-VENT PIPES-PIPES ARE IN CONTACT WITH TOP OF TRUSSES-PROVIDE MINIMUM 1" CLEARANCE 4) DO NOT LET REFRIG. LINES TOUCH THE STEEL FHA STRAPS AT TOP PORTION PLATE |
|
| 10/20/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RETURN NOT TO CEILING IN HALLWAYS. 2. SECURE SUPPLY OUTLETS TO STRUCTURE. 3. FRESH AIR INTAKE NOT CONNECTED/SUPPORTED 4. NOT FRAMED FOR ATTIC ACCESS 5. RETURN AIR NOT CONNECTED APPEARS TO BE INCOMPLETE. |