Permit: T06CM00976

Parcel: 11517223C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00976

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AC DISCON. #2 NEEDS TO BE CORRECTED - PROPERLY SECURE TO WALL.
2. RANGE CONDUCTORS IN PANELS TO BE CONNECTED - REINSTALL RANGE RECEPTS
3. INSTALL SM DETECTOR IN HALL ON UNIT #2
05/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP FLEX LINES TO AC'S,
AC #2 DISCONNECT CORRECT SUPPORT - 1 SCREW THRU SLOT
2. UNIT 1 -- NEED 2 GFI CIRCUIT FOR COUNTERTOPS
3. UNIT 1 -- LIGHT TO BE ENCLOSED TYPE AND 12" AWAY FROM SHELF
4. CONDENSATE PUMP NOT TO BE WIRED INTO FURNACE TO BE ON ITS OWN PLUG TO RECEPTACLE
5. CONNECT WIRING IN PANELS TO BREAKERS (RANGE)
6. UNIT # ITEMS 3 & 4 ALSO APPLY
7. TRANSFORMERS FOR DOORBELLS CANNOT BE IN CLOTHES CLOSET.