Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC DISCON. #2 NEEDS TO BE CORRECTED - PROPERLY SECURE TO WALL. 2. RANGE CONDUCTORS IN PANELS TO BE CONNECTED - REINSTALL RANGE RECEPTS 3. INSTALL SM DETECTOR IN HALL ON UNIT #2 |
|
| 05/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP FLEX LINES TO AC'S, AC #2 DISCONNECT CORRECT SUPPORT - 1 SCREW THRU SLOT 2. UNIT 1 -- NEED 2 GFI CIRCUIT FOR COUNTERTOPS 3. UNIT 1 -- LIGHT TO BE ENCLOSED TYPE AND 12" AWAY FROM SHELF 4. CONDENSATE PUMP NOT TO BE WIRED INTO FURNACE TO BE ON ITS OWN PLUG TO RECEPTACLE 5. CONNECT WIRING IN PANELS TO BREAKERS (RANGE) 6. UNIT # ITEMS 3 & 4 ALSO APPLY 7. TRANSFORMERS FOR DOORBELLS CANNOT BE IN CLOTHES CLOSET. |