Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM00973
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/19/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) #2 ABOVE ROOF MOUNTED FRESH AIR RETURN DUCT MUST BE 10' FROM PLUMBING VENT |
|
| 07/18/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) BEARING STUD AT RANGE EXHAUST DUCT HAS BEEN CUT |
|
| 07/13/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CABINET LAYOUT MAY REQUIRE ADDITIONAL RECEPTACLE LEFT OF OVENS. IF BREAKFAST BAR TO BE INSTALLED, REMOVE RECEPT 2) EAST A/C MAKEUP AIR WITHIN 10' OF SEWER VENT; MOVE OR RAISE VENT 2' ABOVE AIR INTAKE |