Permit: T06CM00967

Parcel: 13323164A


Addresses:

7150 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM00967

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
CAP OK
05/18/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PIPE WRAPS OK
WATER TEST WASTE & VENT IN VISION CENTER TO POINT OF EXISTING VENT CONNECTION OK.
1. NEED TO SEE CAP ON TEST WYE IN CEILING ON VENT. WATER PIPING OK VISION CENTER.
05/17/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
SPOKE TO PLUMBERS CON SITE ABOUT CORRECTIONS.
05/15/2006 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER CONTRACTOR JOSE #817-676-4992
05/15/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
05/12/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL PER APPROVED PLAN OR REVISE IT.
PROVIDE CORRECT MATERIAL TYPES PER EXISTING.
PROVIDE CORRECT DRAINAGE SYSTEMS WITH FITTINGS INSTALLED IN CORRECT DIRECTION FOR FLOW.
HAVE YOUR PLUMBER ON SITE FOR RE-INSPECTION.
05/11/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PLASTIC DWV THREADED FITTINGS CANNOT BE CONCEALED.
- PROVIDE WATER TEST ON VENTS TO POINT OF CONNECTION TO EXISTING VENT.
- PROVIDE PROPER SLOPE ON VENTS.
- ELIMINATE TRAP AND RECEPTOR IN CEILING AT W.H.
- SUPPORT DWV AT EVERY BRANCH AND AT 4' INTERVALS.
- EXPOSE TIE IN PANT OF WASTE CONNECTIONS.
- PROTECT PLASTIC PENETRATING SLAB W/FOAM WRAP.
- SUPPORT AND SECURE WATER PIPING.
- OK TO INSULATE HW.