Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 METAL NOT APPROVED. 2. USE TERMINAL END FOR CONNECTION OF STRANDED WIRE TO SCREW TERMINATIONS. 3. PLEASE VERIFY MANUFACTURERS LISTING FOR ON EXHAUST FAN. 4. USE APPROVED LISTED FITTINGS FOR NON-METALLIC FLEX AND TIGHTEN. 5. PROTECT NON-METALLIC FLEX FROM SHARP EDGES. |