Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM00967
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/24/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE EXCEPT AS NOTED 1. WE STILL HAVE OVERFILL OF CONDUCTORS. |
|
05/22/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABLING TO BE AS PER 725.3 & 6/800.3 &6 2. WHEN USING MANUFACTURERS CLIPS THEY MUST BE EFFECTIVE AND USE ALL CLIPS. IF SCREWS USE 4 ON CORNERS OR 2 ON CENTER. 3. WHEN SUPPORT WIRES ARE USED THEY MUST BE ATTACHED BOTH ENDS 300.11 ALSO CANNOT BE ON CEILING SUPPORT WIRES. 4. PLEASE VERIFY BOX FILL. 5. TIGHTEN LOOSE FITTINGS. 6. FULLY SECURE SUPPORT WIRES - TWIST 7. NEED 2 SUPPORT WIRES PER 2X4 FIXTURES. |