Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/11/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE MC CABLE PER N.E.C 2. MC CONNECTOR NEEDS TO BE REPLACED W/SINGLE CONNECTOR WHRE ONLY ONE MC CABLE IS USED. 3. INSTALL 10 MIL. TAPE WHERE MC CABLE & COPPER WATER LINES MAY MAKE CONTACT. 4. PROVIDE LETTER FROM ELEC. ENGINEER OF RECORD APPROVING THE USE OF MC CABLE. |