Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STILL HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTOR NEC 250.6 2. NEED TO BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE NEC 250.24 (B) |
|
| 04/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. THERE IS OBJECTIONABLE CURRENT ON BONDING CONDUCTOR IN PANEL, DISCONNECT - NEC 250.6 (GROUNDING IN PARALLEL WITH NEUTRAL). 2. INSTALL METAL ADDRESS LABEL ON NEW EQUIPMENT. 3. IN PANEL BOND EQUIPMENT GROUND TO ENCLOSURE. 4. IDENTIFY ATM DISCONNECT AS "ATM DISCONNECT". 5. AT ATM - TIGHTEN LUG FOR BOND AND MAKE SURE GROUNDS AND NEUTRALS ARE ISOLATED IN PANEL |