Permit: T06CM00944

Parcel: 11704311A


Addresses:

522 N 4TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STILL HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTOR NEC 250.6
2. NEED TO BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE NEC 250.24 (B)
04/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. THERE IS OBJECTIONABLE CURRENT ON BONDING CONDUCTOR IN PANEL, DISCONNECT - NEC 250.6 (GROUNDING IN PARALLEL WITH NEUTRAL).
2. INSTALL METAL ADDRESS LABEL ON NEW EQUIPMENT.
3. IN PANEL BOND EQUIPMENT GROUND TO ENCLOSURE.
4. IDENTIFY ATM DISCONNECT AS "ATM DISCONNECT".
5. AT ATM - TIGHTEN LUG FOR BOND AND MAKE SURE GROUNDS AND NEUTRALS ARE ISOLATED IN PANEL