Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM00930
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TEST WATER, DWV AND TUBS/SHWRS OK SAFETY PLATES MISSING AT WATER SERVICE, PLAN SPECIFIES 1" WATER LINE TO WH 3/4 WATER SERVICE CREATES A RESTRICTION CORRECT WATER SERVICE SIZE, INSTALL SAFETY PLATES. OK TO COVER SUBJECT TO PLAN REVISION RECALL ROUGH AND INTERMEDIATE INSPECTIONS BEFORE FINAL INSPECTION AFTER REVISING PLAN AND SECURING CLOSET FLANGES |
|
| 07/26/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - GAS PIPING INSTALLED PER REDLINES - PRESSURE TEST OK - ADD GAS TO PERMIT, REVISE PLAN. - PRESSURE TEST REQUIRED AFTER CONCEALMENT. - PLAN SPECS COPPER WATER PIPING - PEX INSTALLED - KIT SINK PLAN CALLS FOR VTR. AAV REQUIRES PLAN CHANGE - SOUTH SHOWER PAN NOT INSTALLED. - WATER TEST SHOWER PANS - 18" OF COPPER REQUIRED BETWEEN SWEAT VALVES & FLEXES AND PEX TUBING. - REMOVE EXCESS FLUX FROM COPPER JOINTS. - HORIZONTAL CHANGE OF DIRECTION ON DRAINAGE PIPING REQUIRES WYE PATTERN FITTINGS. - USE SWEEP ON KIT TRAP ARMS - SECURE ICE MAKER BOXES - CLOSET FLANGES SHALL BE FASTENED TO FLOOR PER UPC IS 5. - KINK ON PEX AT SOUTH TUB. - BANK PLATES MISSING |