Permit: T06CM00930

Parcel: 111051710

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM00930

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TEST WATER, DWV AND TUBS/SHWRS OK
SAFETY PLATES MISSING AT WATER SERVICE,
PLAN SPECIFIES 1" WATER LINE TO WH
3/4 WATER SERVICE CREATES A RESTRICTION
CORRECT WATER SERVICE SIZE, INSTALL SAFETY PLATES.
OK TO COVER SUBJECT TO PLAN REVISION
RECALL ROUGH AND INTERMEDIATE INSPECTIONS BEFORE FINAL INSPECTION AFTER REVISING PLAN AND SECURING CLOSET FLANGES
07/26/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- GAS PIPING INSTALLED PER REDLINES - PRESSURE TEST OK
- ADD GAS TO PERMIT, REVISE PLAN.
- PRESSURE TEST REQUIRED AFTER CONCEALMENT.
- PLAN SPECS COPPER WATER PIPING - PEX INSTALLED
- KIT SINK PLAN CALLS FOR VTR. AAV REQUIRES PLAN CHANGE
- SOUTH SHOWER PAN NOT INSTALLED.
- WATER TEST SHOWER PANS
- 18" OF COPPER REQUIRED BETWEEN SWEAT VALVES & FLEXES AND PEX TUBING.
- REMOVE EXCESS FLUX FROM COPPER JOINTS.
- HORIZONTAL CHANGE OF DIRECTION ON DRAINAGE PIPING REQUIRES WYE PATTERN FITTINGS.
- USE SWEEP ON KIT TRAP ARMS
- SECURE ICE MAKER BOXES
- CLOSET FLANGES SHALL BE FASTENED TO FLOOR PER
UPC IS 5.
- KINK ON PEX AT SOUTH TUB.
- BANK PLATES MISSING