Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00930
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ARC FAULT NOT TESTING 2. STRAP FLEX FOR AC DISCONNECT 3. PROPERLY IDENTIFY (AT BOTH ENDS) EQUIPMENT GROUND FOR AC'S (BOTH) WILL HAVE REFEE IF NOT CORRECT NEXT INSPECTION. |
|
| 01/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. AT ROOFTOP UNITS A. HAVE UNDERSIZED EQUIPMENT GROUNDS FROM DISCONNECT TO UNITS - NEC 250.122 B. MOUNT W.P RECEPTACLE BOX SO IT DOES NOT HINDER CLOSING/OPENING DISCONNECT COVER. C. STRAP FLEX TO UNITS. 2. SMOKE DETECTOR ARC FAULT NOT WORKING (NO TES) 3. PANEL DIRECTORY STILL NOT CORRECTLY IDENTIFIED 4. COUNTERTOP (KITCHEN) TO BE NO MORE THAN 24" FROM SINK OR END OF COUNTER - REMEMBER NEXT TIME (NEC 210.52) 5. TIGHTEN ALL LOOSE DEVICES |
|
| 12/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR UNIT #1 ONLY -- CHECK SAME IN OTHER UNIT 1. FINISH ROOFTOP WIRING 2. PROVIDE ARC FAULT PROTECTION FOR SMOKE DETECTORS 3. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 4. REPLACE CRACKED DEVICES 5. INSTALL ALL BULBS 6. HOOD NEEDS CONNECTOR FOR ROMEX 7. DISHWASHER WIRING NOT COMPLETE |