Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 11/27/2006 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
| 11/24/2006 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1. NO UFER INSPECTION COMPLETED -- PLEASE VERIFY IF NOT HAVE ARCHITECT REVISE PLANS SHOWING GROUNDING METHOD PER 250.50 2. CONNECT WATER BONDS 3. NEED ACCESS TO INTERIOR TO CHECK SUB-PANEL CONNECTIONS. |