Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 10/25/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) PENDING RETROFIT GREAT ROOM AT FINAL FRAME |
|
| 10/20/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADD BRACED PANEL NORTH WALL OVER 25' SPAN 2) BLOCKING MISSING PER DETAIL 1/D2 3) MISSING HARDWARE PER DETAIL 2/D2 4) NAIL PROTECT PLUMBING 5) MISSING A35 PER DETAIL 3/D2 6) MISSING HOLDOWN GREAT ROOM RETRO FIT REQUIRED |