Permit: T06CM00912

Parcel: 136126470


Addresses:

9945 E LURLENE DR

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/09/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
30 PSI TEST FROM BUILDING APPLIANCE VALVE & FLEX BACK TO WHERE REGULATOR LOCATION AT SOUTHWEST CORNER LOCATION IS OK
1. PROVIDE 30" MINIMUM HORIZONTAL METALLIC PIPING THAT HAS FACTORY APPROVED COATING PRIMED THEN TAPED ON UNDERGROUND PORTION OF PIPING WITH TRANSITION TO PE PIPING & RETEST.
2. PROVIDE FIRE INSPECTION APPROVAL OF TANK PRIOR TO COVERING.