Permit: T06CM00906

Parcel: 122132200


Addresses:

3962 E PIMA ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/16/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
05/15/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE PROVIDE CONTACT # IF NECESSARY FOR ACCESS
05/11/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SHOWER DRAIN CONNECTION AND TUB WASTE AND OVERFLOW LEAKING.
PROVIDE PERM CAP ON ABANDON VENT
05/08/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
WATER TEST OK
-2" WASTE FOR SHOWER, TUB AND LAUNDRY CONNECT TO
2" ABANDON WASTE LINE NOT EXISTING 3" BUT 6 FIXTURE UNITS IS OK FOR 2" WASTE.
- CAP OR REMOVE ABANDONED VENT IF THRU ROOF.
- SUPPORT SHOWER TRAP ARM AT TRAP.
- PROVIDE TEST ON TUB WASTE.
- PROTECT ABS FROM UV DAMAGE W/LATEX PAINT.
03/23/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. TUB, SHOWER AND LAUNDRY DRAINS REQUIRE PROPER VENTING LAUNDRY HAS BEEN REPIPED.
2. PROPER DRAINAGE FITTINGS REQUIRED. A SANTEE ON ITS BACK IS NOT ACCEPTABLE. 1/4 BENDS FOR HORIZONTAL CHANGES OF DIRECTION ARE NOT ACCEPTABLE.
3. PLAN SHOWS NEW 2" DRAIN CONNECTING TO 3" EXISTING
PLUMBER HAS CONNECTED TO VENT.
4. PRESSURE TEST REQUIRED ON DWV
PROPER SUPPORT OF ABS REQUIRED
5. VACUUM BREAKERS ON HAND HELD SPRAYERS REQUIRED.
6. EXPANSION TANK ON WATER HEATER REQUIRED.