Permit: T06CM00880

Parcel: 141093340


Addresses:

8040 S TATE LP


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM00880

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2006 BUILDING - FINAL Approved IVRS - Inspection :*
10/30/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
10/27/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL ALL CIRCUITS IN ELECTRIC PANEL
2) ALL GARAGE OUTLETS MUST BE GFCI PROTECTED OR DEDICATED OUTLETS
3) POWDER ROOM OUTLET LOOSE
4) KITCHEN OUTLETS LOOSE
5) ? ROMEX CANNOT BE EXPOSED IN KITCHEN CABINETS
6) AIR HANDLER REQUIRES MINIMUM 60 AMP-MAX 70 AMP CIRCUIT PRESENTLY 50 AMP #6 CIRCUIT
7) SECURE PORCH ELECTRIC CONDUIT