Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM00880
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
05/24/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWN SIDE OF HOUSE SOUTH OF WINDOW WRONG LOCATION 2) ALL HEADERS NEED TO COMPLY WITH DETAIL 1/5 3) PORCH VIGAS MISSING H2.5 AND BLOCKING 4) MISSING CLIPS ON STUDS ABOVE HEADER THRU OUT 5) ALL EXTERIOR MISSING CLIPS AT TOP ENDS 6) NEED DETAIL FOR BEAM AT FRONT PORCH 7) SHEAR NOT NAILED TO PLAN 8) UNDER SIZED PIECES OF OSB ON GARAGE SHEAR 9) NEED DETAIL FOR CONNECTION OF GARAGE LOWER ROOF TO HOUSE 10) WIND BRACING REQUIRES 2-16D'S EACH END 11) PLAN DO NOT CALL FOR MECHANICAL ON ROOF REVISE PLANS 12) NO ROOF ACCESS |